An entry fitting can fit the cutout and still leave too little room for the cable to bend or the wrench to reach the lug. To specify a busway end tap box, compare the gland plate drawing with a section view in the installed orientation.
An end cable tap box provides a cable connection at the end of a low-voltage busway run. It can feed the busway, and some designs also serve outgoing cables. For an outgoing connection, confirm that the manufacturer permits the application and check how the conductors are protected on the project’s one-line diagram. Match the busway model, end joint, voltage and current ratings, and conductor arrangement to the manufacturer’s approved configuration. The UL 857 scope includes tap boxes and feed boxes among busway fittings.
Key Takeaways
- Show the installed entry face, the cutout locations, and the conductor groups that pass through them.
- Match each lug to the conductor schedule and draw its mounting pattern and cable approach.
- Review the hardest lug to reach with the actual cables and tools shown in the planned installation order.
Specify the Cable Entry and Gland Plate
Choose the Entry Face and Plate
Follow the site cable or conduit route to an entry face the busway manufacturer permits. The gland plate is the panel that carries the entry fittings. On its drawing, identify the installed orientation and the side shown, such as the outside face looking into the box. Dimension the holes from two named reference edges so the shop can locate them with the plate removed.
Confirm which panel takes the entry fittings and which panels provide access to the lugs. On the drawing, distinguish factory cutouts from openings approved for field work and record the manufacturer’s machining limits for that housing.
Match the Fitting to the Cable or Conduit
Select the fitting for the wiring method and cable construction. For a cable gland, check the actual cable diameter against the sealing range and verify the armor range if the gland grips armor. For conduit, size the cutout from the selected hub or connector’s mounting drawing.
Specify the cutout shape, size, center coordinates, and tolerances. Show the space needed for the fitting, seal, and locknut. Mark areas kept clear for the cover gasket, stiffeners, and mounting hardware. Select closures for unused openings that suit the required enclosure Type.
Map Conductor Groups to the Openings
Label each cutout or raceway with its circuit and conductor set. For single-conductor AC cables entering a ferrous plate, show how the phase conductors and any neutral and equipment grounding conductors are grouped to limit induction heating. Have the electrical designer check the layout, including parallel sets and separate openings, against the locally adopted code. Confirm the plate material and permitted opening layout with the busway manufacturer.
On a sample drawing, opening E1 is the side-plate entry for feeder F1. List the selected conduit hub by part number next to E1. Repeat E1 for F1 in the cable schedule and show its phase conductors landing at terminals A1, B1, and C1. Include the neutral and equipment grounding points where applicable. The terminal schedule should identify the approved lug part number at each position. If the entry moves, update the plate drawing and cable schedule together so the shop and installer can trace the same route.

Specify Lugs and Terminal Mounting
Match the Lugs to the Conductor Schedule
A lug joins a cable conductor to a busway terminal. For each phase, neutral, or equipment grounding connection shown on the schedule, verify that the manufacturer-approved lug accepts the conductor size, material, and stranding. Check the permitted number of conductors per lug opening, including when parallel sets are used. Verify that the conductor ampacity used for sizing is compatible with the equipment’s termination temperature rating and the locally adopted code.
Use the dimensions of the selected lug on the layout. Two lugs rated for the same conductor can have different barrel lengths and mounting footprints. For compression lugs, specify the approved crimp tool and die where applicable.
Detail the Mounting Interface and Clearances
Show how each lug attaches to the busway terminal and, where used, how the support bracket or insulator mounts to the enclosure. Mark the hole pattern, hardware, lug barrel direction, phase positions, neutral and grounding terminals, and required enclosure bonding.
Use the specified tightening values for the lug mounting fastener and the conductor clamp where both apply. Check electrical clearances from the installed lugs and hardware to adjacent live parts and grounded metal. Confirm that insulating barriers can be refitted. Coordinate the detail with the busway interface drawing.
For an enclosure-only order, E-Abel’s customized electrical enclosures can be made with project-specific cutouts, gland plates, and mounting plates.

Verify Cable Bend Space and Tool Access
Check the Cable Path
Use a section view to trace the cable from the inside end of the entry fitting to the lug. Include the fitting’s projection, cable supports, and neighboring conductors. When sizing the enclosure, start with the tightest path and use the dimensions of the installed parts.
Check wire bending space at the lug against equipment and project requirements. Confirm that the proposed cable path meets the minimum bend radius in the cable manufacturer’s data and applicable code. If the cable will be pulled under tension, verify the expected pulling tension and sidewall pressure against the cable manufacturer’s limits.
Check the Termination Sequence
Plan the termination sequence around the manufacturer’s instructions. At each step, check that the socket can seat and the wrench can turn with the cables already in place. If crimping takes place inside the box, allow room for the jaws to open and close. Leave space to remove the cover and refit the barriers.
In a side-entry tap box, both rows of cables may fit in their final positions, yet a front-row cable can block the wrench needed to tighten a rear lug’s conductor clamp. Measure the maximum inward projection of the fitting or locknut perpendicular to the inside face of the entry plate. Account for that projection when checking wire bending space, cable bend radius, and access to the rear lug.
Check whether the manufacturer permits terminating the rear row first. If the approved procedure calls for removing a lug before wiring, allow room to remove and reinstall it. If access is still limited, review an approved change to the entry position or enclosure depth, then recheck both cable paths and tool clearance.

What to Approve Before Fabrication
List assumptions on the budget quote and resolve any that affect the build before releasing the fabrication drawings. If different suppliers provide the enclosure and electrical assembly, agree who approves each deliverable before ordering. For more on purchase scope, see the tap-off box enclosure buyer’s guide.
| Deliverable | Approval evidence | Typical reviewer |
|---|---|---|
| Installed arrangement drawing | Accepted busway model, end interface, and site orientation | Busway supplier and project design team |
| Entry plate drawing | Approved cutout revision and the party responsible for machining | Fabricator and electrical designer |
| Terminal section and parts list | Accepted part numbers, cable paths, and access for the installation sequence | Assembly supplier and installing contractor |
| Fabrication release record | Drawing revision, supply boundaries, applicable voltage, current and short-circuit ratings, and certification documents | Buyer and supplier of the complete assembly |
For a tight layout, parallel cable sets, or a replacement enclosure, agree on a first-article fit check before production. Use the specified hardware and tools with representative cable or a dimensionally equivalent mock-up. Check that the locknut can be installed, the tool can engage and move at the least accessible lug in the planned sequence, and the cover can be removed and refitted after routing. For a representative termination, use the specified lug and conductor and follow the manufacturer’s installation instructions, including any specified torque. Record the fit and termination results separately against the drawing revision under review.
Record any substituted lug or fitting, or any moved cutout, on the revised drawing. Recheck the interfaces and approvals affected by that change. If an entry fitting changes, verify its projection into the box, tool clearance, and suitability for the required enclosure Type, even if the cutout size stays the same. For alterations to installed equipment, check what the manufacturer permits and confirm with the local authority whether a field evaluation is needed.
Verify that the specified entry fittings and closures maintain the required enclosure Type. Where the project requires a certified busway fitting, check that the certification record covers the exact end tap box model and assembled configuration.

FAQs About Busway End Tap Boxes
What should I send for a replacement busway end tap box quote?
Send the busway make and model, installed orientation, and a dimensioned entry-plate sketch. Include the cable schedule and lug part numbers if available. Specify whether you need the enclosure alone or the complete fitting.
Can I drill a new cable entry hole in a busway end tap box?
Check whether the manufacturer permits field machining on that plate and at the proposed location. Before cutting, confirm that the entry fitting and opening meet the required enclosure Type and any applicable certification conditions.
How do I size the cutout for a cable gland?
Select the gland using the cable’s actual outside diameter and check the armor range if the gland grips armor. Use the selected gland’s mounting drawing for the cutout diameter and tolerance.
Can I replace mechanical lugs with compression lugs in an end tap box?
Yes, if the manufacturer approves the compression lug for that fitting and conductor. Compare the mounting pattern and barrel length, then check the remaining cable space and access for the specified crimp tool.
How much wire bending space does a busway end tap box need?
Check the requirements for the selected box, lug configuration, and conductor arrangement. On a section drawing, verify the cable’s minimum bend radius and confirm that the tool can reach the lug in the planned installation sequence.
Does UL 857 apply when I order only the end tap box enclosure?
UL 857 covers busway fittings, including end tap boxes. For an enclosure-only order, specify the required enclosure Type and confirm who will provide certification documentation for the complete fitting if the project requires it.
Conclusion

Resolve cable routing and tool access before the shop cuts the plate. Moving an opening after machining can mean reworking or replacing the entry plate.
If you need a custom end tap box enclosure, contact E-Abel with the busway model, installed orientation, and any entry or termination sketches you have. These details help us review the cutout and mounting provisions and clarify what belongs in the enclosure quote.